Search for a Goodman flash code chart and you will find a dozen pages confidently listing one flash as ignition failure, two as a pressure switch, three as a pressure switch the other way round. Those pages disagree with each other, and more importantly they disagree with Goodman.
Goodman has shipped several different diagnostic systems. Older and simpler boards blink a diagnostic light. Current single-stage 80 percent furnaces display alphanumeric error codes. The modulating 96 percent furnaces use a seven-segment display and hold a fault history you can scroll back through. A chart that gives one meaning to one blink cannot be right for all three.
The authority is the legend printed on the label inside your furnace’s access panel, next to the control board. That label is specific to your model. Everything below is what Goodman publishes, and your label wins if the two ever disagree.
This is transcribed from the error code status table in Goodman’s own service and troubleshooting manual for 80 percent gas furnaces. Codes read left to right across the display.
| Display | What Goodman says it means |
|---|---|
| E E E | Internal faults or IRQ loss |
| E E 0 | Lockout due to excessive ignition retries (three) and recycle |
| E E 1 | Pressure switch stuck closed |
| E E 2 | Pressure switch open |
| E E 3 | Open high limit switch |
| E E 4 | Flame detected when no flame should be present |
| E E 5 | Open fuse |
| E E 6 | Low flame signal |
| E E L | Ignitor relay fault |
| E E A | Reversed line polarity or grounding error |
| E E b | Internal gas valve error |
| E E C | External gas valve error |
| E E n | Ignitor open |
| E E J | Inducer relay error |
| E E H | Twin error |
| E 1 1 | Open rollout switch |
| E b L | Low circulator current |
| E b U | Circulator current unexpected |
| E A F | A2L refrigerant communication alarm |
| E A L | A2L refrigerant leakage alarm |
| E A S | A2L internal alarm |
| E A r | A2L relay alarm |
Transcribed from Goodman service and troubleshooting manual RS6621301. Read the codes left to right. Your model's own label is the authority.
Goodman publishes the full manual as a PDF, and it is worth having open if you are standing in front of the furnace: Goodman service and troubleshooting, 80 percent gas furnaces.
On single-stage 80 percent furnaces, Goodman states that the ignition control diagnostic light flashes six times to indicate a trip of the flame rollout switch, and notes that on some models this also indicates an open control board fuse.
A rollout switch opens because flame came out of the burner compartment where it should not. Goodman lists over-firing and flame impingement on the heat shield as causes. That is a combustion fault, not a reset-it-and-see fault.
A real fraction of furnace faults are airflow, and airflow is the one part of this a homeowner can address without tools or risk.
We cover Goodman and Amana along with everything else, and the same licensed team handles the furnace, the gas piping and the electrical circuit, so no part of the job waits on a second contractor. Start with furnace repair if the unit is worth repairing, or furnace installation if the code is the latest in a run of them.
If the pattern is annual and getting worse, HVAC maintenance is what breaks it. Most of the codes above come from a dirty flame sensor, a blocked condensate drain or a restricted filter, and all three are on the maintenance checklist.
We are across New Hampshire, southern Maine and New Jersey. Our largest New Hampshire coverage runs out of Manchester and Dover.
Tell us what you need - we’ll confirm your appointment and get your home back to comfortable, fast.
HOW QUICKLY CAN WE SERVE YOU?